AS-Interface safety module VAA-2E-KE1-S
Производитель: Pepperl+Fuchs
Артикул: VAA-2E-KE1-S
KE1 safety module for the control cabinet, 2 Safety-related inputs
Datasheet excerpt: Technical data of VAA-2E-KE1-S
| Product Description |
|---|
| KE1 safety module for the control cabinet, 2 Safety-related inputs |
| General specifications | ||
|---|---|---|
| Node type | Safety node | |
| AS-Interface specification | V2.11 | |
| Required gateway specification | ≥ V2.0 | |
| Profile | S-0.B | |
| IO code | 0 | |
| ID code | B | |
| ID1 code | F | |
| ID2 code | 0 | |
| UL File Number | E87056 | |
| Functional safety related parameters | ||
| Safety Integrity Level (SIL) | SIL 3 / PL e | |
| MTTFd | 200 a | |
| Indicators/operating means | ||
| LED FAULT | error display; LED red red: communication error or address is 0 | |
| LED PWR | AS-Interface voltage; LED green | |
| LED IN | switching state (input); 2 LED yellow | |
| Electrical specifications | ||
| Rated operating voltage | 26.5 ... 31.6 V PELV from AS-Interface | |
| Rated operating current | ≤ 70 mA | |
| Protection class | III | |
| Input | ||
| Number/Type | 2 safety-related inputs for mechanical contacts, cross-circuit monitored: 2 single-channel contacts: up to category 2 / PL c according to EN ISO 13849-1 or 1 two-channel contact: up to category 4 / PL e according to EN ISO 13849-1 Cable length must not exceed 300 m per input. | |
| Supply | from AS-Interface | |
| Voltage | 20 ... 30 V DC pulsed | |
| Current loading capacity | input current limited ≤ 15 mA, overload and short-circuit resistant | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 62026-2:2013+A1:2019 | |
| Standard conformity | ||
| Insulation coordination | EN 50178:1998 | |
| Electromagnetic compatibility | EN 61000-6-2, EN 61000-4-5 1 kV asymmetric, criterion B, EN 61000-6-4 | |
| Degree of protection | EN 60529:2000 | |
| Fieldbus standard | EN 62026-2:2013+A1:2019 | |
| Electrical safety | EN 50178:1998 IEC 60204-1:2007 | |
| Emitted interference | EN 61000-6-4:2001 | |
| AS-Interface | EN 62026-2:2013 | |
| Functional safety | Category 4 / PL e to EN ISO 13849-1:2015 SIL 3 according to IEC 62061:2015 and IEC 61508 Part 1-7:2010 | |
| Standards | NFPA 79:2002 | |
| Ambient conditions | ||
| Ambient temperature | -25 ... 50 °C (-13 ... 122 °F) | |
| Storage temperature | -25 ... 85 °C (-13 ... 185 °F) | |
| Shock and impact resistance | 10 g, 16 ms in 6 spatial directions 1000 shocks | |
| Vibration resistance | 0.75 mm 10 ... 57 Hz , 5 g 57 ... 150 Hz, 20 cycles | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Connection | removable terminals, terminal connection ≤ 2.5 mm2 | |
| Material | ||
| Housing | PA 66-FR | |
| Mass | 80 g | |
| Mounting | DIN mounting rail | |
Classifications
| System | Classcode |
|---|---|
| ECLASS 13.0 | 27272603 |
| ECLASS 12.0 | 27242604 |
| ECLASS 11.0 | 27242604 |
| ECLASS 10.0.1 | 27242604 |
| ECLASS 9.0 | 27242604 |
| ECLASS 8.0 | 27242604 |
| ECLASS 5.1 | 27242604 |
| ETIM 9.0 | EC001599 |
| ETIM 8.0 | EC001599 |
| ETIM 7.0 | EC001599 |
| ETIM 6.0 | EC001599 |
| ETIM 5.0 | EC001599 |
| UNSPSC 12.1 | 39121535 |