Application
| Application | hygienic systems; I/O modules for field applications |
| Daisy-chain function | power supply; fieldbus interface |
Electrical data
| Operating voltage [V] | 20...28 DC; (US ; to SELV/PELV) |
| Current consumption [mA] | 300...3900; (US) |
| Protection class | III |
| Additional voltage supply [V] | 20...30 DC; (UA) |
Actuator supply UA
| Max. current load total [A] | 8 |
| Current rating per port [A] | 2; (adjustable: 0...2; Factory setting: 2) |
Sensor supply US
| Max. current load total [A] | 3.6 |
| Current rating per port [A] | 2; (adjustable: 0...2; Factory setting: 0,45) |
Inputs / outputs
| Total number of inputs and outputs | 16; (configurable) |
| Number of inputs and outputs | Number of digital inputs: 12; Number of digital outputs: 12 |
Inputs
| Number of digital inputs | 12; (IO-Link Port Class A: 4 x 2; IO-Link Port Class B: 4 x 1) |
| Switching level high [V] | 11...30 |
| Switching level low [V] | 0...5 |
| Digital inputs protected against short circuits | yes |
Outputs
| Number of digital outputs | 12; (IO-Link Port Class A: 4 x 1; IO-Link Port Class B: 4 x 2) |
| Short-circuit proof | yes |
Actuator supply UA
| Max. current load per output [mA] | 2000 |
Sensor supply US
| Max. current load per output [mA] | 2000 |
Interfaces
| Communication interface | Ethernet; IO-Link |
Ethernet - PROFINET
| Transmission standard | 100Base-TX |
| Transmission rate | 100 MBit/s |
| Protocol | PROFINET |
| Factory settings | | IP address: 0.0.0.0 | | subnet mask: 0.0.0.0 | | gateway IP address: 0.0.0.0 | | MAC address: see type label | |
| Note on interfaces | | IO-Link Integration Edition 2 | | CC-C (Conformance Class C) (IRT-Switch) | | S2 redundancy | | Netload Class III | | CiR (Configuration in Run) | | SNMP (Simple Network Management Protocol) | | MRP (Media Redundancy Protocol) | | Supported network topologies: line | | ring | |
IO-Link Master
| Transmission type | COM1 (4,8 kBaud); COM2 (38,4 kBaud); COM3 (230,4 kBaud) |
| IO-Link revision | 1.1 |
| Number of ports class A | 4 |
| Number of ports class B | 4 |
Operating conditions
| Ambient temperature [°C] | -25...60 |
| Storage temperature [°C] | -25...85 |
| Max. relative air humidity [%] | 90 |
| Protection | IP 65; IP 66; IP 67; IP 69K; (operation with stainless steel protective caps: IP 69K) |
| Protection rating (NEMA 250) | 6P |
| Pollution degree | 2 |
| Chemical media | | ISO 16750-5 | HLP, CC, DB, DC, DD, CA | | NEMA 250 5.13.1 | AA | |
Tests / approvals
| EMC | | EN 61000-6-2 | | | EN 61000-6-4 | | |
| Shock resistance | |
| Vibration resistance | | DIN EN 60068-2-64 2009-04 | | | DIN EN 60068-2-6 2008-10 | | |
| MTTF [years] | 43 |
Mechanical data
| Weight [g] | 434.8 |
| Materials | housing: PA grey; socket: stainless steel (1.4404 / 316L) |
| Sealing material | EPDM |
Accessories
| Items supplied | | Protective cap: 1 x M12, stainless steel, E12542 | |
Remarks
| Remarks | | For further information please see the operating instructions. | |
| Pack quantity | 1 pcs. |
Electrical connection - Ethernet
| IN / OUT XF1, XF2 | Connector: M12; coding: D; Sealing: EPDM |
Electrical connection - Process connection
| IO-Link Port Class B X1...X4 | Connector: M12; coding: A; Sealing: EPDM |
Electrical connection - power supply IN
| XD1 | Connector: M12; coding: L |
Electrical connection - power supply OUT
| XD2 | Connector: M12; coding: L; Sealing: EPDM |